Sinotek ® for you around the Temperature control specialists, quality optimization master
TECHNICAL DATA
Model
| LS202F | LS203F LS203S | LS205F LS205S | LS207F LS207S | LS210F LS210S | LS215F LS215S | LS220F LS220S | LS230F LS230S | LS240F LS240S |
TEMPERATURE(℃) | 5-35 |
COOLING OUTPUT(kcal/h) | 6300 | 7900 | 13051 | 21100 | 27700 | 42200 | 55400 | 72928 | 110800 |
COMPRESSOR | HIGH EFFICIENT HERMETIC COMPRESSOR IMPORTED WITH SILENCER INSIDE |
INPUT POWER(kW) | 2.5 | 3 | 5 | 8 | 10 | 8×2 | 10×2 | 14×2 | 10×4 |
PEFRIGERANT GAS | R22 |
FAN(kW) | 0.19 | 0.19×2 | 0.19×2 | 0.46×2 | 0.46×2 | 0.70×2 | 1.32×2 | 1.32×3 | 1.32×3 |
CONDENSER | AIR-COOLED | HIGH EFFICIENT FINNED COIL | “V”HIGH EFFICIENT FINNED COIL |
WATER-COOLED | SHELL-AND-TUBE WITH REMOVABLE COVER PLATE |
EVAPORATOR | SHELL-AND-TUBE WITH REMOVABLE COVER PLATE |
PUMP(kW) | AIR-COOLED WATER-COOLED | 0.62 | 0.85 | 1.08 | 1.15 | 1.95 | 3.12 | 3.35 | 3.58 | 3.58 |
* | 0.4 | 0.75 | 1.5 | 1.5 | 2.2 | 2.2 | 3.7 | 3.7 |
MAX.FLOW RATE(L/min) | AIR-COOLED WATER-COOLED | 58 | 135 | 135 | 170 | 235 | 235 | 235 | 235 | 235 |
* | 90 | 160 | 250 | 250 | 400 | 400 | 600 | 600 |
MAX.PRESSURE(Mpa) | AIR-COOLED WATER-COOLED | 0.40 | 0.30 | 0.40 | 0.30 | 0.30 | 0.40 | 0.50 | 0.60 | 0.607 |
* | 0.128 | 0.138 | 0.172 | 0.172 | 0.203 | 0.203 | 0.237 | 0.237 |
SAFETY GUARD | COMPRESSOR OVERLOAD/CIRCULATING PUMP/FAN OVERLOAD/HIGH/LOW PRESSURE FREON SHORTAGE PROTECTOR/COOLING WATER SHORTAGE/HIGH/LOW WATER TEMPERATURE/INSUFFICIENT ENERGY/BREAK PROTECTOR/SUPPLEMENTARY WATER INLET/REDUCER AND PRESSURE REGULATING UNIT/BREAKER THERMAL PROTECTOR |
CHILLING WATER(L) | AIR-COOLED WATER-COOLED | 40 | 40 | 60 | 120 | 120 | 140 | 200 | 310 | 270 |
* | 50 | 85 | 140 | 140 | 200 | 200 | 400 | 300 |
DIMENSIONS(cm) | AIR-COOLED
WATER-COOLED | 88×65×124 | 133×65×117 | 133×65×117 | 166×85×165 | 166×85×165 | 194×99×201 | 216×100×212 | 311×115×203 | 311×137×235 |
* | 100×60×106 | 120×60×115 | 145×65×131 | 145×65×131 | 175×78×165 | 175×78×165 | 205×95×185 | 230×100×223 |
WEIGHT(kg) | AIR-COOLED WATER-COOLED | 180 | 300 | 340 | 420 | 520 | 650 | 720 | 1500 | 1800 |
* | 220 | 320 | 420 | 440 | 730 | 780 | 1650 | 1800 |
COOLING WATER | WATER-COOLED | * | 1″ | 11/4″ | 11/2″ | 11/2″ | 2″ | 2″ | 2×2″ | 2×2″ |
CHILLING WATER | AIR-COOLED WATER-COOLED | 1″ | 11/4″ | 11/4″ | 11/2″ | 11/2″ | 2″ | 2″ | 2″ | 2″ |
* | 1″ | 11/4″ | 11/2″ | 11/2″ | 2″ | 2″ | 2″ | 2″ |
POWER | 3PH 380V 50HZ |
MAX.POWER(kW) | AIR-COOLED WATER-COOLED | 3.6 | 4.23 | 6.46 | 10.1 | 12.87 | 20.5 | 26 | 35.5 | 47.54 |
* | 3.4 | 5.8 | 9.5 | 11.5 | 18.2 | 22.2 | 31.7 | 43.7 |
1.S for water-cooled F for wind-cooled
2.Cooling output testing term:at the evaporating temperature of5℃,Condensing temperature of50℃
5.Specifications between 1 and 300RT are available.